EJA510A EJA530A Absolute and Gauge Pressure transmitter
Features :
The absolute and gauge pressure transmitter model EJA510A and EJA530A can be used to measure
liquid, gas, or steam pressure. Both output a 4 to 20 mA DC signal corresponding to the measured pressure, and also feature remote setup and monitoring through communications with the BRAIN™ terminaland CENTUM CS™ or µXL™ or HART® 275 host.
Specifications :
Supply Voltage “”
10.5 to 42 V DC for general use and flameproof type
10.5 to 32 V DC for lightning protector (Optional
code /A)
10.5 to 30 V DC for intrinsically safe, Type n,
nonincendive, or non-sparking type
Minimum voltage limited at 16.4 V DC for digital
communications, BRAIN and HART
Load (Output signal code D and E)
0 to 1335 for operation
250 to 600 for digital communication
EMC Conformity Standards “” ,
EN61326-1 Class A, Table2 (For use in industrial
locations)
EN61326-2-3
European Pressure Equipment Directive 97/23/EC
Sound Engineering Practice
With option code /PE3
Category III, Module H, Type of Equipment: Pressure
Accessory-Vessel, Type of Fluid: Liquid and Gas,
Group of Fluid: 1 and 2
Communication Requirements “”
BRAIN
Communication Distance
Up to 2 km (1.25 miles) when using CEV polyethylene-insulated PVC-sheathed cables. Communication
distance varies depending on type of cable used.
Load Capacitance
0.22 F or less (see note)
Load Inductance
3.3 mH or less (see note)
Spacing from power line
15 cm or more.
Input Impedance of communicating device
10 k or more at 2.4 kHz.
Technical parameters :
Products show :